Enhance the performance of your HVAC system with the Astar ABB ACH580 HVAC IP21 1.5kW 400V 3ph AC Inverter Drive. This innovative drive offers precise control with HMI, while DBr provides smooth and efficient operation. It also includes STO for safety and C2 EMC technology for compliance with regulations. If repairs are needed, our team specializes in providing quality service for optimal product functionality.

Contact us to inquire about this product

If you love this product and wish for a customized quote contact us at number +9190449 0777 and we will be happy to provide you with more info!

Add To Inquiry

Category:

Description

ABB ACH580 HVAC series AC Inverter for 1.5kW (2HP) 400V 3 Ph motor to 3.8A when Fan/Pump rated. Operates in VxF or Sensorless Vector control and converts fixed frequency Three Phase 400V input to variable frequency 400V to control the speed of a standard AC induction motor, permanent magnet synchronous motor or synchronous reluctance motor.

Output Current: 3.8A
Peak Output Current: 5.9A for 2 seconds at startup.
Overload: 110% x 60 seconds every 10 minutes.

Size R1: 125mm Wide x 223mm Deep x 373mm High.
IP Rating: IP21.
Weight: 4.6kg

Speed Control Range: 0 to 500Hz.
Braking (DBr): Internal Brake Switch Fitted; External braking resistor (not supplied) to minimum 52 Ohms, maximum 1.4kW – see linked products below for compatible option.

Keypad (HMI): Removable Assistant Control Panel ACH-AP-H included – multi-lingual with multi-line LCD Display.
2 x Analogue Inputs, 2 x Analogue Outputs, 6 x Digital Inputs, 3 x Relay Contact sets.
Fieldbus: BACnet MS/TP, Modbus RTU and N2. (Twin wire)
Safe Torque Off: Terminals for dual channel SIL3/PLe STO. (Linked out as default)

Input Current: 4A.
Input Voltage: 380 to 480V three phase +-10% at 50/60Hz.
Input Fuse: 6A. gG (IEC) fuse can be used if operation time is less than 0.5s. See manual for uR or aR alternatives.
Built in choke to minimise supply harmonics.
EMC Compliance: to EN61800-3 1st Environment, C2 (Industrial and restricted domestic)

Cubicle Mount.
Rated Ambient: 40℃.
Ventilation Space: Above: 150mm, Below: 86mm, Sides: 150mm, Front: Not Given
Heat Loss at max output: 66W.
Mounting: via 4 x slotted holes at rear for M5 screws on 317mm x 98mm centres.

Full part number: ACH580-01-04A1-4

Previous part number: ACH580-01-04A0-4. Same rating but dimensions are different.

Please note ACH550 to ACH580 ratings do not necessarily match. This listing is rated at or above the Output Current of the previous generation ACH550-01-04A1