ABB ACH580 HVAC IP21 160kW 400V 3ph AC Inverter Drive, HMI, STO, C2 EMC ACH580-01-293A-4

Upgrade your HVAC system with the powerful Astar AC Inverter Drive! Our ABB ACH580 drive supports up to 160kW of power and runs on 400V 3-phase electricity. Plus, the intuitive HMI makes setup and maintenance a breeze. Feel secure with the STO safety feature and shield your equipment with the C2 EMC option. Need a repair? Our reliable repair service has got you covered.

Contact us to inquire about this product

If you love this product and wish for a customized quote contact us at number +9190449 0777 and we will be happy to provide you with more info!

Add To Inquiry

Category:

Description

ABB ACH580 HVAC series AC Inverter for 160kW (200HP) 400V 3 Ph motor to 278A when Fan/Pump rated. Operates in VxF or Sensorless Vector control and converts fixed frequency Three Phase 400V input to variable frequency 400V to control the speed of a standard AC induction motor, permanent magnet synchronous motor or synchronous reluctance motor.

Output Current: 278A
Peak Output Current: 418A for 2 seconds at startup.
Overload: 110% x 60 seconds every 10 minutes.

Size R8: 300mm Wide x 393mm Deep x 965mm High.
IP Rating: IP21.
Weight: 69kg

Speed Control Range: 0 to 500Hz.
Braking (DBr): External Braking Unit can be fitted to DC Terminals if required

Keypad (HMI): Removable Assistant Control Panel ACH-AP-H included – multi-lingual with multi-line LCD Display.
2 x Analogue Inputs, 2 x Analogue Outputs, 6 x Digital Inputs, 3 x Relay Contact sets.
Fieldbus: BACnet MS/TP, Modbus RTU and N2. (Twin wire)
Safe Torque Off: Terminals for dual channel SIL3/PLe STO. (Linked out as default)

Input Current: 293A.
Input Voltage: 380 to 480V three phase +-10% at 50/60Hz.
Input Fuse: 425A. gG (IEC) fuse can be used if operation time is less than 0.5s. See manual for uR or aR alternatives.
Built in choke to minimise supply harmonics.
EMC Compliance: to EN61800-3 1st Environment, C2 (Industrial and restricted domestic)

Cubicle Mount.
Rated Ambient: 40℃.
Ventilation Space: Above: 155mm, Below: 300mm, Sides: 150mm, Front: Not Given
Heat Loss at max output: 3936W.
Mounting: via 4 x slotted holes at rear for M8 screws on 658mm x 262mm centres.

Full part number: ACH580-01-293A-4

Please note ACH550 to ACH580 ratings do not necessarily match. This listing is rated at or above the Output Current of the previous generation ACH550-01-246A