Description
Welcome to our top-quality GC800 Repairing Service! If you’re experiencing malfunctions or damages in your device, we’ve got you covered. Our skilled technicians will fix your device using the latest techniques and genuine parts, ensuring optimal performance and longevity. Trust us to get your gadget back to its prime shape, and enjoy its features like never before.
Are you tired of dealing with a faulty GC800? Don’t fret, our GC800 Repairing Service will make everything right for you. We’re a team of passionate technicians dedicated to restoring your device’s functionality and aesthetics. Be it software or hardware issues, we’re equipped with the expertise and equipment to diagnose and fix them swiftly. Give us a try, and experience the difference.
- Full graphics back-lit LCD display with power save mode
- Supports Auto (AMF, remote start/stop and cyclic modes) and manual modes
- Monitors 1-Ph/3-Ph voltage, frequency and load current for generator and mains; monitors 1-Ph/3-Ph power factor
for generator
- Offers ‘’Auto exercise mode’’ (2 events) to start and stop the genset for preconfigured time
- Monitors engine safety parameters through analog resistive
sensors and digital input switches (e.g. – lube oil pressure, engine temperature, fuel level)
- Controls start relay, fuel relay, stop relay, alarm hooter and more
- Supports the battery charging alternator I/O interface
- MPU interface for engine speed measurement
- Versatile software capable of saving “events” during operation; event log for 100 events with real time clock (RTC) stamps and engine run hour information
- GC800 has built-in electronic governor module which directly connects to SEDEMAC’s rotary actuators* to guarantee speed governing performance as per ISO8528:G3 class
GC800 Controller…………………………….. SM0007264
.
SPECIFICATION :
Operating/Storage Temperature
-20˚C to 65˚C/-30˚C to 70˚C, as per IEC 60068-2-1, 2
Vibration
2G in X, Y and Z axes, as per IEC 60068-2-6
Humidity
0% to 95% RH, as per IEC 60068-2-78
EMI/EMC
Compliance as per IEC 61000-6-2, 4
Power Supply
8V – 32V DC continuous; power transients as per ISO 7637-2
Ingress Protection
IP65 for front face with optional gasket, as per IEC 60529
Shock
15 g for 11 mS, compliance as per IEC 60068-2-27
Technical
Maximum Standby Current
~0.08A @ 12V or 24V DC
Crank-start Dropout Survival Period
50 mS for a drop from 12V DC
Charging Alternator Interface
0.25A @ 12V DC; 0.125A @ 24V DC
Diagnostic voltage measurement
Digital Output
6 x 0.75A high-side drivers configurable for pre-heat, hooter, etc
Digital Input
5 switch-to-ground inputs configurable for lube oil, temp, fuel level, etc
Analog Input
3 resistive inputs (10Ω – 1000Ω); fully configurable for various sources
1 analog input (2.5V ± 2V) for E-Governor speed bias and paralleling or can be used as 0 – 5V analog sensor
E-governor Module Interface
Output for rotary actuator
(2.5V ± 2V) input for target speed bias; 2.5V for zero bias